Output |
|
115V Models |
230V Models |
Power Levels crated
at nominal inputs |
2000VA/1250W, 2700VA/1700W
4000VA/2500W |
2000VA/1250W, 2700VA/1700W
4000VA/2500W, 5000VA/3200W |
Output Voltage |
100V/110V/115V/120V Selectable |
200V/220V/230V/240V Selectable |
Voltage Waveform |
Sine wave |
Crest Factor |
3:1 |
Output Frequency
(Synchronized to Mains) |
Auto Select for 50/60Hz
47Hz ~ 55Hz for 50Hz nominal
56Hz ~ 65Hz for 60Hz nominal |
Regulation (Nominal) |
±5% typical of nominal voltage (optional at ±8% AVR for wide I/P up to ±35%) |
Regulation (Batt. mode) |
±3% of selected output voltage (adjustable with the remote set-up software) |
Transfer time |
Blackout 3ms typical
Brownout 1ms typical
Battery mode to Normal mode:1ms typical |
Over current protection |
Over load alarm level 100% ~ 120%
Over load shutdown level 120% ~ 190%
(Adjustable with the remote set-up software) |
Input |
|
115V Models |
230V Models |
Nominal Voltage |
100V/110V/115V/120V Selectable |
200V/220V/230V/240V Selectable |
Input Frequency |
47Hz ~ 65Hz, 50/60Hz auto-sensing |
Efficiency (Normal mode) |
97% |
Noise Filtering |
Full time EMI/RFI filtering |
Over current protection |
1100VA:by AC fuse
1650VA ~ 4000VA:by re-settable over current protector |
1100VA ~ 2200VA:by AC fuse
3300VA ~ 4000VA:by re-settable over current protector |
Voltage Range |
-20% ~ +24% for selected nominal voltage.
-29% ~ +33% adjustable with the remote set-up software |
AVR Range
(2 Bucks, 2 Boosts) |
Enhanced Buck: +15% of selected nominal voltage
Buck mode: +5% of selected nominal voltage
Boost mode: -5% of selected nominal voltage
Enhanced Boost: -12.5% of selected nominal voltage |
Surge Protection |
2000VA ~ 4000VA:324 Joules |
2000VA:440 Joules
4000VA ~ 5000VA:660 Joules |
Battery |
Battery type |
Maintenance–free sealed, valve-regulated, Lead-Acid |
Voltage |
2200VA/2700VA:48Vdc
4000VA/5000VA:72Vdc |
Typical backup time at half-load |
No Limit |
Typical backup time at full load |
No Limit |
Charging method |
Smart pulse charging with two charging modes.
Quick charging when battery is not fully charged, trickle charging when battery is 90% fully charged. |
Average charging current |
11A at normal line and normal temperature (Average) |
Average charging voltage for each battery |
Quick charging mode:14V maximum.
Trickle charging mode:13.2V ~13.9V adjustable with the remote set-up software. |
Protection |
Over current protection (SCR control)
Over charging voltage protection (SCR control)
Thermal protection (CPU control)
When temperature inside UPS is over 45℃, charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging. The cycle will be repeated until the temperature is lower than 44℃. |
Monitoring |
Smart monitoring & warning for failed battery or open-circuit battery.
Auto-detection each time when power on or every 6 days. |
Communications & Management |
Standard Interface port |
UPSilon2000 compatible.
RS232, USB, |
Optional Interface port |
DB9 SNMP, RJ45 (Surge Protection) |
Control panel |
LCD |
Audible alarm |
Alarm on battery:Low battery & Battery over voltage
Alarm on abnormal operation:Over load, Short-circuit, & Over heat |
EBT (Estimation of Backup
Time) system |
Yes |
Green mode function (Auto-shutdown during blackout) |
1% to 14% of full load (adjustable with the remote set-up software)
The default setting is OFF. |
Environmental and Safety |
Operating Temp. |
Up to 1500 meters:0℃ to 40℃ (32℉ to 104℉) |
Transit/storage Temp. |
-15℃ to 55℃ (5℉ to 131℉) |
Relative Humidity |
5 - 95% non condensing |
Operating Altitude |
0 ~ 3000 meters |
Audible noise |
≦50 dBA |
Safety Markings |
BSMI |
CE |
EMC |
Class B, EN50091-2, FCC part15, IEC1000-2-2 |
Quality control system |
ISO 9001 |
Physical |
Dimensions:
Unit / Shipping
(H x D)/H×D×W (cm) |
2000VA ~ 4000VA:3u x 45cm / 59 x 33 x 59(cm)
5000VA:4u x 48cm / 64 x 40 x 60(cm) |
Weight:
Net / Gross (kg) |
2200VA/2700VA:26 / 30 (kg)
4000VA:34 / 38 (kg)
5000VA:44 / 48 (kg |
Packing |
Export carton for each unit, 16~30 units per pallet |
|