Index > Product > ON Line UPS > UKT 6KVA ~ 20KVA

UKT 6KVA ~ 20KVA

Online UPS - UKT 6KVA ~ 20KVA

ONLINE UPS " Tower Ver. " UKT 6KVA ~ 20KVA.

Feature :

  • Online double conversion
  • High reliability DSP control
  • Advanced PFC technology
  • Wide input voltage range
  • DC cold start function
  • Intelligent fan speed control
  • Full protection function
  • Intelligent RS232 /RS485 Communication Port
  • SNMP adapter or Dry contacts (optional)
  • Advanced no-master-slave parallel technology (optional)
  UKT6000 /UKT6000L UKT1110 /UKT1110L UKT3110 UKT3115 UKT3120
 INPUT
Input power factor ≧0.99 ≧0.95
Input Voltage Range(V) 120-276:
50% load: 120-276
75% load: 150-276
100% load: 176-276
208-478:
50% load: 208-478
75% load: 260-478
100% load:305-478
Phase Single phase(L,N,G) Three phase in single Phase out(L1,L2,L3,N,G)
Bypass range(V) 180-255
Frequency range(Hz) 45-55
Battery voltage(Vdc) 120 240
 OUTPUT
Output Power(KVA/KW) 6/4.2 '10/7 15/10.5 20/14
Output Voltage(VAC) 220/230/240 ±2%
Output frequency(Hz) 50/60 ±1%(battery mode)
Output wave form Pure sine wave
THD THD ﹤3% (Linear load)
Switch time(ms) 0
Efficiency 88%(linear load) 90%(linear load)
Over load(in main) 105%~130% load 1min.
131%~150% load 30S.
﹥150% load 300mS
105%~125% load 10 mins.
126%~150% load 1min
﹥150% load1S
Crest Factor '3:1
 OTHER FEATURES
DC cold start Yes
Display LCD:Input/Output voltage, battery voltage, load capacity, UPS working status.
LED Indicator:Utility, Battery, Bypass, Fault
Communication RS232 port RS232/RS485 port
SNMP adapter(Optional) Network Monitor through SNMP adapter
Protection Protection for input over voltage, input low voltage, low battery, over load,fault, short circuit,
over temperature.
Alarm Battery low, main abnormal, UPS overload, fault
Noise(dB) ﹤60
Dimension(WxDXH(mm)) 253x637x700 / 253x637x500 253x637x700
Weight(Kg) 95/30 100/34 35 52 55