Power Value(Ⅱ)(10~400KVA)

Power Value(Ⅱ) 3phase in 3phase out Online LF UPS 10~400KVA)

Power Value(Ⅱ) 3phase in 3phase out Online LF UPS (10~400KVA)

Powervalue (Ⅱ) is upgraded DSP controlled Online LF UPS with output isolation transformer.
It can be your perfect large capacity power shield for your critical and industrial load.

QUALITY POWER SUPPLY:

WF PV(II)series is an On-Line double conversion (VFI) UPS with isolation output transformer, unit capacity from 10KVA to 400KVA. It is immune to the interferences on the electric power supply line as it has special input and output filters. World leading DSP technology, with high speed DSP processor are adopted to guarantee system’s high stability and giving stable output power supply for all kinds of harsh load.

PERFECT APPLICAITON:

Middle and large data center, Telecom, Finance, Traffic, Defense, Medical, Education, Energy, Manufacture, Industry, etc.

MAXIMUM RELIABILITY :

The advanced DPS technology appliance considerably improves reliability, since a reduction in electronic components lowers the likelihood of breakdowns. Digital control is provided by the microprocessor that, in the PV(II) series controls all the internal parameters, thus increasing reliability and performance. In parallel connections, digital control ensures balance of the currents, which generally change over time due to phenomena such as vibrations and temperature, between the UPS units and the exchange of information with no need for manual tuning. MTBF >200,000h.PV(II) has been designed so that it can be connected in parallel even after the installation of the first unit. The power availability can be increased thanks to various configurations available such as the parallel configuration, the Dual Bus function and the Dynamic Dual Bus system.

HIGH SPEED DSP PROCESSOR:

Ensuring the operation more fast and stable

OUTPUT 100% UNBALANCE LOAD:

The ups can accept 3phase 100% unbalance load to satisfy kinds of load configuration.

ECO function:

under good power condition, UPS can work in ECO mode, efficiency reach 98%, green and energy saving;

UPS FOR INDUSTRIAL LOADS:

PV-Plus with its strong overload capability, output galvanic isolation and low harmonic current distortion, is the ideal solution for industrial applications. Thanks to the high battery current, PV Plus Series is suitable to work with large battery banks as it can guarantee recharging in 10 hours as recommended by the battery manufacturer.

OPERATING FLEXIBILITY:

All power ratings of the PV(II) series can also be used as Frequency Converters 50 to 60 Hz and vice versa.

COLORFUL MULTIFUCTIONAL PANEL:

The 7 inch colorful multifunctional panel allows easy and humanized operation of the UPS. It gives access to the most important parameters: status and alarms, control commands, input, output, battery measurements (power, current, voltage, frequency and temperature) and settings. The PV(II) series’ diagnostics system includes up to 128 alarms or messages allowing precise and detailed identification of any event.

Advanced Battery Management (ABM):

Optimal battery management includes:

  • Periodic battery test, and automatically transfer between boost charging and float charging to extend battery lifespan
  • Automatically adjusting the battery charging current according to battery capacity
  • Recharge temperature compensation (optional)
  • Remaining back up time display

MAXIMUM SAFETY FOR PERSONNEL:

The back feed protection device prevents any voltage back feed in the upstream distribution board, thus ensuring the safety of the maintenance personnel.

FULL FRONT ACCESS AND CONVENIENT CABLE CONNECTION:

Full frontal access is for all power and electronic components, which reduces the floor space required and consequently reduces the installation costs.

Configured with top and bottom cable connection

PERFECT HUMAN-MACHINE COMMUNICATION:

UPS Monitor software displays the most important information such as the input and output voltage, the load applied, the remaining back-up time, etc., in the form of bar graphs. The software is able to provide information even in the event of a failure, in support of the fault diagnostics. The UPS Monitor software can be used to program the automatic shutdown of all open systems in the event of a prolonged black out. PV Plus can also operate with a network agent for applications on LAN or WAN networks.

The UPS contains the following hardware interfaces:

  • RS232 /RS485 interface,
  • Dry contacts: battery low,battery discharge,bypass/breakdown
  • EPO (Emergency Power Off) contact for UPS shutdown using the remote emergency button.
  • SNMP card(optional)

ADVANCED PARALLEL:

Maximum parallel up to 8 units and share the common battery pack.10-80kVA parallel with parallel card only ; 100kVA-400kVA, parallel card with weaver reactance and different capacity UPS can be also be parallel;

DYNAMIC DUAL BUS SYSTEM:

Two independent systems set in Dual Bus Configuration can be merged together at any time for system expansion or maintenance. This provides a lot of flexibility in your installation in case of maintenance or when it is necessary to change the redundancy level of both systems.

EVENT LOG:

1000 historical events can be saved, which is easy for tracing ups operation status and useful for maintenance

Technical specification:

(1) 10-120KVA specification:

Model PV3310ii PV3315ii PV3320ii PV3330ii PV3340ii PV3360ii PV3380ii PV33100ii PV33120ii
Capacity 10kVA 15kVA 20kVA 30kVA 40kVA 60kVA 80kVA 100kVA 120kVA
system
Output PF  0.8(lag)
System efficiency  (inverter mode) 92%(@100% load) ;90% @50%load;
System efficiency  (ECO mode) 98%(@100%load)
Maximum leakage current 100(mA)
MTBF Above 200,000hours
Dry contact  Standard: 3 types signal(BAT. low,battery mode,bypass /failure);
Optional:14 dry contact ; output: 12Vdc 80mA
Communication interface Standard RS232,optional: RS485 / MODBUS
Operation temperature 0 ~ 40 °C
Humidity 95 % (non-condense)
Cooling Forced air(speed varying according to load percent)
Max. altitude Within 1000m(every 100increase,capacity decrease -1%),Maximum 4000m
Noise (dB) 52 ~ 58
IP protection
(EN 60529)
IP20
Input/output way Bottom /rear
Safety standard safety:GB4943 ,EN 50091-1;EMI:GB7260.2,GB/T 17626.2~5EMC, EN 50091-2
Physical
W *D*H(mm) 600*600*1280 800*800*1480 800*800*1800
Weight(Kg) 195 210 220 305 340 500 600 800 950
AC input
Rated voltage  380/400/415VAC  Three-phase four-wires
Input voltage range ± 15 %- ± 25 % adjustable)
Rate frequency 50 / 60 Hz  auto-sense
Frequency range 50/60Hz+/-5Hz
Input soft start function 0 - 100%,10-300s(settable)
Input power factor Reachable 0.99(plus harmonic filter)
Input current harmonic component(THDi ) Can <5%(plus harmonic filter)
Max. input current [A] 18 27 36 54 72 108 144 180 216
The output characteristic of the rectifier
Maintain the voltage (20°C) Battery type1 and 2 :V =435Vdc (2.266 x el.)
Battery type 3 :V =424Vdc (2.21 x el.)
 Battery type 0:the voltage value between type 1and 2,
Voltage regulating range: V =400~460Vdc
Charging voltage (20°C) Battery type1 and 2 :V (%recharging<95%) = 445Vdc (2.32 x el.)
Battery type 3 :V (%recharging<95%) = 460Vdc (2.4 x el.)
Battery type 0: the voltage value between type 1and 2,
Voltage regulating range: V =400~460Vdc
The highest charging voltage 445V
The charger output voltage regulation accuracy 1%
DC ripple voltage component ≤1%
Battery
Unit number(rated voltage) 384VDC(360-384v,selectable)
Charging current settings 0.1C(battery capacity)
The battery discharge end voltage Battery type 1,2 and 3:no-load discharge current,V min=346 [V dc]
Battery type 1,2 and 3:output current =Ah capacity,V min=316 [V dc]
Battery type 1,2 and 3:output current >Ah capacity,V min=306 [V dc]
Battery type 0: the factory set the default values,V min=320 [V dc]  
Regulating range: V min =300~360[V dc]
Inverter output
Rated capacity  [kVA] 10 15 20 30 40 60 80 100 120
Rated power  [kW] 8 12 16 24 32 48 64 80 96
Rated voltage  [V]  380/400/415VAC  three-phase four-wire
Rated current  [A] 12 18 24 36 48 72 96 120 144
Phase voltage setting 200 ~ 244 V (control board)
Peak factor 3:1
Voltage phase shift (degrees)       100% balanced load ± 1'
Voltage phase shift (degrees)
100% unbalanced load
± 2'
Phase voltage difference         100% balance load ± 1 %
Phase voltage difference         100% unbalanced load ± 3 %
(THD v) <2% (linear load), <5%(non-linear load)
Steady-state voltage stability ± 1 %
Transient voltage response ± 5 % within 10ms
Rated frequency Same as input
Frequency stability When asynchronous,± 0.5 %;synchronization,± 2 %
(can be set to ± 1~5 %,by the panel operation)
Overload   600’ / 10’ / 1’ (110/125/150% rated current)
Short circuit 0.1s Double input
Inverter efficiency(load 100%) 98%
Bypass
Rated capacity  [kVA] 10 15 20 30 40 60 80 100 120
Rated voltage  [V]  380/400/415VAC Three-phase four-wires
Input voltage range ±15 %(can be adjusted from the control panel ± 10 %,± 20%)
Rated frequency       [Hz] 50 / 60
Frequency range ±2 %(can be adjusted from the control panel ± 5 %)
“STAND-BY ON”(Eco mode, the bypass switch to inverter)transfer time 2~5ms
Inverter/bypass transfer time <1ms
Overload 10’/1’/18” (150/175/200% Rated current)
Standard configuration Feed flow protection, bypass independently isolated

(2) 160-400KVA product specification parameter table:

Model PV33160 ii PV33200 ii PV33250 ii PV33300 ii PV33350 ii PV33400 ii
Capacity 160kVA 200kVA 250kVA 300kVA 350kVA 400kVA
6 pulse 12 pulse 6 pulse 12 pulse 6 pulse 12 pulse 6 pulse 12 pulse 6 pulse 12 pulse 6 pulse 12 pulse
System parameter
Output power factor  0.8(lag)
Overall efficiency (normal model)                 Load 100% 94%
Load 50% 92%
Overall efficiency:
(ECO mode)              Load 100%
98%
Maximum leakage current(mA) 100
Standby economic model Standard functions
Mean time before failure(MTBF) Above 200,000 hours
Dry contact signal  Standard three control signal (battery low,battery discharge,bypass/breakdown);
Optional 14 control signal;output 12Vdc 80mA
Computer monitors port Standard S232,optional ODBUS
Running temperature 0 ~ 40 °C
Maximum relative humidity 95 % (non-condensing)
Cooling Forced ventilation (fan speed changing with load)
Maximum altitude 1000m rated power(Rising 100m lower 1%) maximum 4000m
Noise dB 54 ~ 62
Protection class
(EN 60529)
IP20
Inlet and outlet of the wire way Bottom /rear
Safety standard  Safety: GB4943,EN 50091-1;electromagnetic compatibility: GB7260.2,
GB/T 17626.2~5EMC,EN 50091-2
Physical parameter
Wide (mm) 1100 1400 1100 1400 1400 1400 1400 1400 1600 1600 1600 1600
Deep*high (mm) 800*1800 1000*2000 1100*2000
Weight(kg) 1200 1550 1350 1750 1500 1950 1650 2150 1850 2400 2100 2700
The input rectifier features
Rated voltage  380/400/415VAC  Three-phase four wires
Voltage range ± 15 % (± 25 % adjustable)
Rated frequency 50 / 60 Hz automatic identification
Frequency range 45 ~ 65
Input power
slow start function
Yes,0 - 100%,can be set to 10-300 seconds
Input power factors cosφ Reachable 0.99(plus harmonic filter)
Input current harmonic component(THDi ) can<5%(plus harmonic filter)
Max.input current [A] 250 315 400 500 550 630
The output characteristic of the rectifier
Maintain the voltage (20°C) Battery type1 and 2 :V =435Vdc (2.266 x el.) Battery type1 and 2 :  
V =544Vdc (2.266 x el.)
Battery type 3 :V =424Vdc (2.21 x el.) Battery type 3 :      
V =530Vdc (2.21 x el.)
Battery type 0:the voltage value between type 1 and 2,
Voltage regulating range: V =400~460Vdc
Battery type 0:the voltage value between type 1 and 2, Voltage regulating range:
V =500~575Vdc
Charging voltage (20°C) Battery type1 and 2 :V (%recharging<95%)=445Vdc (2.32 x el.) Battery type1 and 2 : V (%recharging<95%)
=557Vdc (2.32 x el.)
Battery type 3 :V (%recharging<95%)=460Vdc (2.4 x el.) Battery type 3 :V (%recharging<95%)
=576Vdc (2.4 x el.)
Battery type 0:the voltage value between type 1 and 2,
Voltage regulating range: V =400~460Vdc
Battery type 0:the voltage value between type 1 and 2, Voltage regulating range:
V =500~575Vdc
The highest charging voltage 445V 556V
The charger output voltage regulation accuracy 1%
DC ripple voltage component ≤1%
Battery
Unit number(rated voltage) 192 units(384VDC) 240 units(480VDC)
Charging current settings 0.1 C(battery capacity)
The battery discharge end voltage Battery type 1,2 and 3:no-load discharge current,
Vmin=346 [V dc]
Battery type 1、2 and 3:no-load discharge current,Vmin=433 [V dc]
Battery type1,2 and 3:output current =Ah capacity,
Vmin=316 [V dc]
Battery type 1、2 and 3:
output current =Ah capacity,
Vmin=395 [V dc]
Battery type 1,2,3:output current >Ah capacity,
Vmin=306 [V dc]
Battery type 1、2 and 3:
output current >Ah capacity,
Vmin=383 [V dc]
Battery type 0:the factory set the default values,Vmin=320 [Vdc]  Regulating range: Vmin =300~360V[V dc] Battery type 0:the factory set the default values,Vmin=400 [V dc] Regulating range:
Vmin =375~450V[V dc]
Inverter output
Rated capacity  [kVA] 160 200 250 300 350 400
Rated power  [kW] 128 160 200 240 280 320
Rated voltage  [V]  380/400/415VAC  three-phase four-wire
Rated current  [A] 195 243 304 365 426 486
Phase voltage setting 200 ~ 244 V (control board)
Peak factor 3:1
Voltage phase shift (degrees)       100% balanced load ± 1'
Voltage phase shift (degrees)
100% unbalanced load
± 2'
Phase voltage difference         100% balance load ± 1 %
Phase voltage difference         100% unbalanced load ± 3 %
THD v <2% (linear load), <5%(non-linear load)
Steady-state voltage stability ± 1 %
Transient voltage response ± 5 % within 10ms
Rated frequency Same as input
Frequency stability When asynchronous,± 0.5 %;synchronization,± 2 %
can be set to ± 1~5 %,by the panel operation)
Overload   600’ / 10’ / 1’ (110/125/150% rated current)
Short circuit 0.1s Double input
Inverter efficiency    (load 100%) 98%
Bypass
Rated capacity  [kVA] 160 200 250 300 350 400
Rated voltage  [V]  380/400/415VAC  three-phase four-wires
Input voltage range ±15 %(can be adjusted from the control panel± 10 %,± 20%)
Rated frequency       [Hz] 50 / 60
Frequency range ±2 %(can be adjusted from the control panel± 5 %)
“STAND-BY ON”(Economic mode, the bypass switch to inverter)conversion time 2~5ms
Inverter/bypass transfer time <1ms
Overload 10’/1’/18” (150/175/200% rated current)
Standard configuration Feed flow protection, bypass independently isolated
NOTE: 120VAC power grid 10-200kVA are available;